Slide ảnh 1
Slide ảnh 2

Product

Programmable universal digital display type M2229

Product code: M2229
Category: Display units
QTY:
hotro

Minh Quan Technology Joint Stock Company

Hotline: 01692 114 683

Mr Que: 0973 852 363

Ms Ha: 0165 2197 433

Email: mqtekvietnam@gmail.com

Call us

Product information

  • Input: U, I, temperature, optional: pH, conductivity, frequency
  • two alarm contacts
  • 4 digit LED display, 14mm
  • programmable by computer
  • buttons to change the alarm contacts
  • power supply 20…253VAC or DC, galvanic isolated
  • signal output, galvanic isolated
  • flush mounting
    Product Details

    The digital display M2229 is used to indicate or monitor any sensor signal. It converts the input sensor signal to a programmable display for example 0 to 100.0%. In this range two alarm contacts can be set independently. A 4-digit LED display shows the actual value and setpoints or alarm values in the range of -1999 to 9999 units. All settings can be set directly at the M2229 or with a personal computer or a laptop. The values of the user menu can be protected from unintended access using an access code.

    Application example:
    A typical application would be to measure and monitor pressure in a process vessel. The pressure transmitter converts the pressure of 1 to 10 bar to a current signal of 4 to 20mA. The M2229 monitors under- and overpressure in the vessel. It converts the 4… 20mA signal current to 0…100.0%. The alarm is set between 0% (=1 bar) and 100.0% (=10 bar). With these floating alarm contacts, overpressure valves, compressors, etc. are driven directly.

    Optionally, a galvanic isolated output signal of 0…20mA or 4…20mA is available.

Specifications

Input signal: M2229-A: 0/4…20mA/0…1V and 10V, programmable

M2229-T: Platinum-/nickel, with 100,200,500 or 1000W at 0°C (DIN 43 760),

in 2- or 3-wire connection

Input load / impedance: current signal=51W, voltage signal=1MW
2-Wire transmitter supply: 24VDC max. 25mA
Display: 4-digit, LED red, 14.2 mm
Display range: -1999…9999
Accuracy: ±0.1% at 23°C ambient temperature
Reproducibility: ±0.1%
Temperature coefficient: zero drift: 30ppM/°C typical,

gain drift: 25ppM/°C typical

Long-term stability: ±0.1%
Working temperature range -5 to +45°C
Maximum humidity: 95%, non-condensing
Range adjustment: by computer programmable, see manual
Zero-/Gain adjustment: by computer programmable, see manual
Option alarm contacts:

Hysteresis:

Contacts:

Max. contact load:

Change alarm contacts

Display alarm contacts:

Mode of the alarm contacts:

two, adjustable between 0,0 and 100,0%

by computer programmable, factory set: ±5 digit, see manual

floating change over contacts

1A/230V resistive

by button switches or computer programmable, see manual

by button switches or computer programmable, see manual

with two red LED-Lamps

Display unit: with one red LED-Lamp
Option signal output:

Max. load:

Output impedance:

0/4…20mA, galvanically isolated

500W

>1MW typical

Power supply: 20 to 253VAC or DC
Power supply load 4.5 to 7.0W at 230VAC
CE-conformity: fulfilled
Terminals: plug-in screw terminals
Terminal description:

 

 

c.o.= change over

n.o.= normally open

n.c.= normally closed

1 = supply voltage: AC~/DC(+)

3 = supply voltage: PE

5 = signal output (-)

7 = not used

9 = signal input (-) / Sensor (-)

11 = signal input current (+) / Sensor (-) Sense

12 = alarm contact 1, n.o. contact

14 = alarm contact 1, n.c. contact

16 = alarm contact 2, c.o. contact

2 = supply voltage: AC~/DC(-)

4 = signal output (+)

6 = signal output PE

8 = 2-Wire transmitter supply +24V

10 = signal input voltage (+) /Sensor (+)

13 = alarm contact 1, c.o. contact

15 = alarm contact 2, n.o. contact17 = alarm contact 2, n.c. contact

 

Mounting: 2 mounting clamps
Weight: 200g
Warranty 2 years

Reviews