Product
Programmable universal digital display type M2229
Minh Quan Technology Joint Stock Company
Hotline: 01692 114 683
Mr Que: 0973 852 363
Ms Ha: 0165 2197 433
Email: mqtekvietnam@gmail.com
Call usProduct information
- Input: U, I, temperature, optional: pH, conductivity, frequency
- two alarm contacts
- 4 digit LED display, 14mm
- programmable by computer
- buttons to change the alarm contacts
- power supply 20…253VAC or DC, galvanic isolated
- signal output, galvanic isolated
- flush mounting
Product Details
The digital display M2229 is used to indicate or monitor any sensor signal. It converts the input sensor signal to a programmable display for example 0 to 100.0%. In this range two alarm contacts can be set independently. A 4-digit LED display shows the actual value and setpoints or alarm values in the range of -1999 to 9999 units. All settings can be set directly at the M2229 or with a personal computer or a laptop. The values of the user menu can be protected from unintended access using an access code.
Application example:
A typical application would be to measure and monitor pressure in a process vessel. The pressure transmitter converts the pressure of 1 to 10 bar to a current signal of 4 to 20mA. The M2229 monitors under- and overpressure in the vessel. It converts the 4… 20mA signal current to 0…100.0%. The alarm is set between 0% (=1 bar) and 100.0% (=10 bar). With these floating alarm contacts, overpressure valves, compressors, etc. are driven directly.Optionally, a galvanic isolated output signal of 0…20mA or 4…20mA is available.
Specifications
Input signal: | M2229-A: 0/4…20mA/0…1V and 10V, programmable
M2229-T: Platinum-/nickel, with 100,200,500 or 1000W at 0°C (DIN 43 760), in 2- or 3-wire connection |
|
Input load / impedance: | current signal=51W, voltage signal=1MW | |
2-Wire transmitter supply: | 24VDC max. 25mA | |
Display: | 4-digit, LED red, 14.2 mm | |
Display range: | -1999…9999 | |
Accuracy: | ±0.1% at 23°C ambient temperature | |
Reproducibility: | ±0.1% | |
Temperature coefficient: | zero drift: 30ppM/°C typical,
gain drift: 25ppM/°C typical |
|
Long-term stability: | ±0.1% | |
Working temperature range | -5 to +45°C | |
Maximum humidity: | 95%, non-condensing | |
Range adjustment: | by computer programmable, see manual | |
Zero-/Gain adjustment: | by computer programmable, see manual | |
Option alarm contacts:
Hysteresis: Contacts: Max. contact load: Change alarm contacts Display alarm contacts: Mode of the alarm contacts: |
two, adjustable between 0,0 and 100,0%
by computer programmable, factory set: ±5 digit, see manual floating change over contacts 1A/230V resistive by button switches or computer programmable, see manual by button switches or computer programmable, see manual with two red LED-Lamps |
|
Display unit: | with one red LED-Lamp | |
Option signal output:
Max. load: Output impedance: |
0/4…20mA, galvanically isolated
500W >1MW typical |
|
Power supply: | 20 to 253VAC or DC | |
Power supply load | 4.5 to 7.0W at 230VAC | |
CE-conformity: | fulfilled | |
Terminals: | plug-in screw terminals | |
Terminal description:
c.o.= change over n.o.= normally open n.c.= normally closed |
1 = supply voltage: AC~/DC(+)
3 = supply voltage: PE 5 = signal output (-) 7 = not used 9 = signal input (-) / Sensor (-) 11 = signal input current (+) / Sensor (-) Sense 12 = alarm contact 1, n.o. contact 14 = alarm contact 1, n.c. contact 16 = alarm contact 2, c.o. contact |
2 = supply voltage: AC~/DC(-)
4 = signal output (+) 6 = signal output PE 8 = 2-Wire transmitter supply +24V 10 = signal input voltage (+) /Sensor (+) 13 = alarm contact 1, c.o. contact 15 = alarm contact 2, n.o. contact17 = alarm contact 2, n.c. contact
|
Mounting: | 2 mounting clamps | |
Weight: | 200g | |
Warranty | 2 years |