The threshold converter M2218 is used to check or control either a signal current or a temperature. A Pt-100 platinum sensor in 3-wire mode can be connected to the unit. It converts the input signal to an internal standard signal of 0 to 100.0%. Two independent limit contacts can be set within this range.
- Input M2218-A: 4…20mA
 - Input M2218-T: Pt-100 0…160ºC
 - 2 alarm contacts
 - programmable
Product Details
The threshold converter M2218 is used to check or control either a signal current or a temperature. A Pt-100 platinum sensor in 3-wire mode can be connected to the unit. It converts the input signal to an internal standard signal of 0 to 100.0%. Two independent limit contacts can be set within this range.
All settings as limit values, hysteresis, range and operating mode of the contacts can be set with a PC-program.
The unit may be programmed to customers values or ranges by the factory.
A typical application would be to measure and monitor pressure in a process vessel:
A pressure transmitter converts the pressure of 1 to 10 bar to a current signal of 4 to 20mA. The M2218 monitors under- and overpressure in the vessel. It converts the 4…20mA signal current to 0…100.0%. The alarm is set between 0% (=1 bar) and 100.0% (=10 bar). With these floating alarm contacts, overpressure valves, compressor relays, etc. are driven directly.If a Pt-100 sensor is connected to the input, the unit works as a temperature monitor or as a simple temperature controller.
Optionally a galvanically isolated output signal of 4…20mA is available.
The 24VDC power supply is galvanically isolated from the input circuit and the output current source.
 
Specifications
| Input signal: | M2218-A: 4…20mA M2218-T: Pt-100 platinum sensor with 3-wire connection, temperature range: 0…160°C | 
| Input load: | M2218-A: 51Ω | 
| Accuracy : | ±0.2% at 23°C ambient temperature | 
| Reproducibility | ±0.1% | 
| Temperature coefficient | Zero drift: 50ppM/°C typical
 Gain drift: 50ppM/°C typical  | 
| Long-term stability | ±0.2% | 
| Working temperature range: | -5 to +45°C | 
| Maximum humidity: | 95%, non-condensing | 
| Programming: | with a programming cable to a front panel miniature plug | 
| Limit contacts:
 Hysteresis: Contacts: Max. contact load Change limit contacts: Display limit contacts:  | 
Two, adjustable between 0.0 and 100.0%
 computer programmable, see manual floating normally open contacts 1A/48V resistive computer programmable, see manual computer programmable, see manual  | 
| Current output:
 Max. load: Output impedance:  | 
4…20mA, galvanically isolated
 <400Ω >1MΩ typical  | 
| Power supply: | 24VDC, 15% | 
| Power supply load: | <2.5W at 25VDC | 
| CE-conformity: | fulfilled | 
| Terminals: | 2 x 7-pole plug-in screw terminals | 
| Case: | DIN-standard case (L x W x H) 90 x 36 x 58mm | 
| Mounting: | 35mm mounting rail, EN50022-35, min. distance from one instrument to the next: 5mm | 
| Weight: | ~90g | 
| Warranty: | 2 years | 