Temperature
Isolating amplifier & line conditioner type M8742/22
Minh Quan Technology Joint Stock Company
Hotline: 01692 114 683
Mr Que: 0973 852 363
Ms Ha: 0165 2197 433
Email: mqtekvietnam@gmail.com
Call usProduct information
- This instrument is no longer on stock and will only be produced on request
- power supply 20…253VAC/DC, galvanically isolated
- 2-wire transmitter supply
Specifications
Input: | See part number list |
Output: | See part number list |
Input Impedance: | – Current input = 50Ω
– Voltage input up to 1V = 1GΩ – Voltage input 1V and up = 100kΩ |
Output Impedance: | – Current output = >1MΩ
– Voltage output = <0.1Ω |
Max. Load at 24mA | 700Ω |
Max. Output Current Limit, Voltage only: | 15mA short circuit proof |
Input, 2-wire Transmitter: | 20VDC max. 25mA |
Special Signal Range: | – Voltage input: ±100mV…±500V, others on request
– Current input: ±10mA…±1A, others on request – Voltage output: ±100mV…+13V/10mA…-6V/4mA – Current output: ±10mA…+25mA/-2mA |
Carrier Ripple: | <10V@10V output |
Bandwidth: | DC…10Hz, -3dB@10Hz |
Internal Oscillator: | »1kHz |
Test Isolation Voltage: | 2500VAC/1′, input Þ output Þ power supply |
Mode of Signal Transfer: | The input is converted to a pulse with modulated digital signal, transmitted to the secondary by means of a pulse transformer and then demodulated to a DC signal |
Common Mode Rejection Ratio: | >140dB@1000VDC
>100dB@1000VAC, measured with the M8742/22-1 |
Gain Error: | <0.05% of full scale |
Zero Offset: | <0.05% of full scale |
Working Temperature Range: | -5…+55ºC |
Supply: | 20 to 253 VDC or AC |
Supply Load: | 2.4W@25mA output |
CE Conformity: | Fulfilled |
Terminals: | Screw terminals, 12-pole for 1.5mm wire |
Mounting | 35mm mounting rail, EN50022-35 |
Weight: | 130g |
Reviews
Related Products
Load cell type M2428-14
Code: Product Details The M2428-14 is a low-cost load cell to measure weights or forces in the range of 25kg (~250N) to 30'000kg (~300'000N). The bending beam consists of a strain gage sensor with integrated electronics to convert the force or weight to a 4…20mA signal. There is no need to use external, sensitive strain gage amplifiers or signal conditioning devices. A cell connects directly to any 2-wire sensor input of process control computers or other control equipment and displays. The bending beam confirms the protected class IP67 an delivered with open cable ends. Any range within the measuring range can be programmed. E.g. 45kg to 420kg = 4 to 20mA within a calibrated range of 0 to 500kg.