Temperature
Isolating low cost Amplifier / Converter Type M2842
Minh Quan Technology Joint Stock Company
Hotline: 01692 114 683
Mr Que: 0973 852 363
Ms Ha: 0165 2197 433
Email: mqtekvietnam@gmail.com
Call usProduct information
- Input signals: 0/ 4…20mA, 0…1/ 10V, Pt100, custom specific signals
- Output signals: 0…1kHz, 0…2kHz
- Loop powered transmitters do not need an extra power supply and can be connected directly
- Measuring range directly reprogrammable on site with a notebook
- Power supply voltage ranges from 20…253VAC/DC, galvanically separated
- 17.5mm narrow din rail enclosure
Product Details
The M2842 low cost isolating amplifier series bring the cost of an analogue input signal down because expensive PLC cards are no longer needed. The convertr can measure almost all known analogue signals (voltage, current, temperature) to a frequency. They are simple programmable with 5 miniature switches and the free Mpro Software from MOSTEC. The output signal is a frequency which is proportional to the input signal.
The instruments have a 3 way galvanic separation of 2.5kV between input / output / supply. The following impulse outputs are standard: NPN, PNP, active signal; all within the voltage range between 5 to 24Vss.A typical application is the isolation and measurement of a temperature with a pt-100 probe. Possibly all your PLC analogue inputs are used up, so you can measure the output frequency of the M2842 with a simple digital input and therefore avoid to attach another analogue card. Like this, you save the whole card for a single temperature measurement. Because the instrument has a built in tree way galvanic separation, there is also no need for a galvanic separation to avoid a possible ground loop.
The instrument has 16 preprogrammed measuring ranges which can be selected with the miniature switches on the side. With the free Mpro software the instrument can be reprogrammed within the range of the instruments specifications. If you order the instrument at MOSTEC, the instrument will be programmed and labeled to your requested range.
Selectable standard ranges:
Input signals: 0…1V, 0…10V, 0…20mA, 4…20mA, -50…300˚C, -30…170˚C, 0…100˚C
Output signals: 0…1kHz und 0…2kHz, higher frequencies on request.Supply:
Universal power supply from 20 to 253VAC/DC, galvanic 3-way separation
Specifications
Input: | Voltage DC: 0…1V, 0…10V, Current DC: 0…20mA, 4…20mA,
Temperature sensor Pt-100: -50…300°C, -30…+170°C, 0…100°C, programmable with the software “Mpro” |
Output: | 0…1kHz and 0…2kHz, others on request, programmable with the software “Mpro” |
Input impedance: | Current input: 22W (= input load)
Voltage input: 1MΩ |
Max. output current limit: | Max. 25mA, short circuit proof |
Special signal range: | Voltage input: ±100mV to ±10VDC, others on request
Current input: ±2mA to ±20mADC, others on request Frequency output: 0…2kHz, other on request |
Temperature sensor:
Max. length of sensor cable: |
Platinum-100 (DIN 43760) in 2- or 3-wire circuit, others on request
3-wire shielded, up to 20W cable resistor, symmetrically (»300m) 2-wire shielded, error depends on cable resistance |
Input, 2-wire transmitter: | 20VDC, max. 25mA |
Test Isolation Voltage: | 2500VAC 1 minute, input -> output -> power supply
4000VAC on request |
Reproducibility: | £0.1% |
Accuracy: | ±0.1% at 23°C ambient |
Temperature coefficient: | Zero drift typ. 20ppM/°C, gain drift typ. 15ppM/°C |
Working temperature range | -5 to +55°C |
Max. humidity: | 95%, non-condensing |
Power supply: | Wide range power supply: 20 to 253VAC or DC |
Power supply load: | 2.0W |
CE-conformity: | fulfilled |
Case: | 17.5mm wide case |
Mounting: | 35mm mounting rail, EN50022-35 |
Weight: | »130g |
Warranty: | 2 years |
Options: | – “Low-cost” versions with reduced functions
– USB programming unit for MOSTEC devices with cable and software – Customer modifications, special ranges |
Reviews
Related Products
Load cell type M2428-14
Code: Product Details The M2428-14 is a low-cost load cell to measure weights or forces in the range of 25kg (~250N) to 30'000kg (~300'000N). The bending beam consists of a strain gage sensor with integrated electronics to convert the force or weight to a 4…20mA signal. There is no need to use external, sensitive strain gage amplifiers or signal conditioning devices. A cell connects directly to any 2-wire sensor input of process control computers or other control equipment and displays. The bending beam confirms the protected class IP67 an delivered with open cable ends. Any range within the measuring range can be programmed. E.g. 45kg to 420kg = 4 to 20mA within a calibrated range of 0 to 500kg.